Backbone Cabling
System Structure
The backbone cabling system provides interconnections between telecommunications
rooms, equipment rooms, main terminal space, and entrance facilities.
It includes backbone cables, intermediate and main cross-connects,
mechanical terminations, and patch cords or jumpers used for backbone-to-backbone
cross-connections. The backbone also extends between buildings in
a campus environment.
Some points specified
for the backbone cabling subsystem include:
Equipment connections to backbone cabling should be made with
cable lengths of 30m (98 ft.) or less.
The backbone cabling shall be configured in a star topology. Each
horizontal cross-connect is connected directly to a main cross-connect
or to an intermediate cross-connect, then to a main cross-connect.
The backbone is limited to no more than two hierarchical levels
of cross-connects (main and intermediate). No more than one cross-connect
may exist between a main and a horizontal cross-connect and no
more than three cross-connects may exist between any two horizontal
crossconnects.
A total maximum backbone distance of 90m (295 ft.) is specified
for high bandwidth capability over copper. This distance is for
uninterrupted backbone runs. (No intermediate cross-connect).
The distance between the terminations in the entrance facility
and the main cross-connect shall be documented and should be made
available to the service provider.
Recognized media may be used individually or in combination, as
required by the installation. Quantity of pairs and fibers needed
in individual backbone runs depends on the area served. Recognized
backbone cables are:
Multi-pair cable is allowed, provided that
it satisfies the power sum crosstalk requirements.
The proximity of backbone cabling to sources of electromagnetic
interference (EMI) shall be taken into account.
Cross-connects for different cable types shall be located in the
same facilities.
Bridged taps and splitters are not allowed.
Notes:
In ISO/IEC 11801:2002, the equivalent cabling elements to the main
cross-connect (MC) and intermediate cross-connect (IC) are called
the campus distributor (CD) and building distributor (BD) respectively.
Interact
>>Ask Siemon
>>Siemon Worldwide
>>Request Catalog
>>Download Literature
>>Get Support
>>Read Case Studies
Locate
Installers & Consultants Let us
match you with consultants and installers in your area >>Learn
More
Start Your Project Right
Your Business Type End User Installer Consultant
Distributor System Integrator Find
Distributors
Zip Code:
Distance:
Within 50 miles Within 100 miles Within 250 miles (worldwide)
|