Twisted-Pair PCords and Cross-Connect
Jumpers
- Patch cords should use stranded cable for
adequate flex-life.
- Stranded cables must meet the minimum performance
requirements for horizontal cable except that 20 percent more
attenuation for UTP is allowed by '568-B.2 and 50 percent more
attenuation is allowed by '11801:2002 for UTP and F/UTP.
- Color-code for cross-connect jumpers: One
conductor white, the other a visibly distinct color such as
red or blue.
- Performance markings should be provided to
show the applicable transmission category in addition to safety
markings.
- Insulated O.D. of stranded wires should be
0.8mm (0.032 in.) to 1mm (0.039 in.) to fit into a modular plug.
- Production performance specifications for
plug cord assemblies are addressed in '568-B.2.
- Color Codes for Stranded, 100¦¸ Patch Cord
|
Option 1 |
|
Option 2 |
|
white/blue - blue |
pair 1 |
green - red |
|
white/orange - orange |
pair 2 |
black - yellow |
|
white/green - green |
pair 3 |
blue - orange |
|
white/brown - brown |
pair 4 |
brown - slate |
- Note:
- Because of their identical pair groupings,
patch cords terminated with either T568A or T568B pair assignments
may be used interchangeably, provided that both ends are terminated
with the same pin/pair scheme.
|
|