TWISTED-PAIR CABLING INSTALLATION
PRACTICES
To avoid stretching, pulling tension should not exceed 110N (25
lb? for 4-pair cables.
Installed bend radii shall not exceed:
4 times the cable diameter for horizontal UTP cables under no load
conditions.
8 times the cable diameter for horizontal ScTP cables.
10 times the cable diameter for multi-pair backbone twisted-pair
cables under no load conditions.
Horizontal cables should be used with connecting hardware and patch
cords (or jumpers) of the same performance category or higher.
Avoid cable stress, as caused by:
cable twist during pulling or installation
tension in suspended cable runs
tightly cinched cable ties or staples
tight bend radii
Important Note: Installed twisted-pair cabling shall be classified
by the least performing component in the link. |
|